MINI BOOMERANG IS A DETECTION SYSTEM PARTICULARLY
ADAPTED FOR THE SMOKE LINE DETECTION IN:
Library and Archives - Museums - Galleries - Building
with decorated ceiling - Churches - Cinemas - Theaters
and conference Halls - Hotels - Hospitals - Schools
- Public buildings - Garages - Artisans buildings
- Little Warehouses and Storerooms - Supermarkets.
MINI BOOMERANG INFRARED BEAM FIRE LINE DETECTION
SYSTEM:
Protects area up to 800 mq. - Sensitivity level fully
adjustable - Reiection of optical and electromagnetic
interference - Instant automatic reset in case of
temporary beam obstructions - No periodic maintenance
- Drastic reduction of installation and connection
costs.
|
The Mini-Boomerang
System consist of three units.
The Transmitter and Receiver (Tx-Rx) placed in a unic
plastic equipment, the Retroreflector Unit, and Control Panel.
An equivalent control unit can be substitute, while the
Mini-Boomerang units are not substitutable.
The Mini-Boomerang Tx emits by a special projector
an infrared beam with a calculated angle. The beams traverses
the protected area and radiated the reflection's unit which
is located on the opposite side, go back precisely onto the
receiver unit objective crossing in reverse way the area so
that protected.
In the event of smoke the information is transmitted to the
Rx. Every bit of smoke information is transmitted to
the control panel unit. The presence of smoke, is seen from
many stand points three of wich are the Rx visibility
reduction, smoke development in frequency, and time of reduction
visibility.
The Mini-Boomerang receiver device senses minute envirinmental
disturbances characteristics of the beginning of a fire and
assesses the information. Ending with the diagnosis of the
information, in the event of a smoke the system triggers the
fire allarm and remain in the allarm state. If the beam is
blocked by an obstacle a hight intensity alarm light goes
on at electronic Mini-Boomerang unit.
All that is not necessary to reset the system when the obstacle
is removed, if others equivalent control panel has not the
trouble memory. The electronic Mini-Boomerang unit
trasmits by relè to the control panel the allarms of fire
and system trouble.
The particular optical construction normally permit a very
good alignement between the electronic and retroreflector's
unit. The system accept a certain angle mistaken, but sametimes
installation reasons request a loosed mounting bracket.
This is available requiring it to our seller Agency.
The installation, alignement and connection of the system
is very simple and does not require special Knowled on the
part of the installer.
After installation, the system is pratically free from periodic
maintenance.
|
MODEL MB2S
|
|
FEATURES
|
| Set of distance choise |
1÷25
m |
26÷40 m. |
| Max
lenght Miniboomerang÷retroreflector |
25
m. |
40
m. |
| Min
lenght Miniboomerang÷retroreflector |
1
m. |
26
m. |
| Closer lenght on request by mean of diaphragm |
YES |
YES. |
| Max
width EN54/14 |
15
m. |
15
m. |
| Max
height suggested |
<=11 m. |
<=11 m. |
| Max
surface EN 54/14/8 |
375
m². |
600 m². |
| Max
volume EN54/14 |
4125
m³. |
6600 m³. |
|
COMMON FEATURES
|
| Storage temp. |
-20°C÷+60°C |
| working temp. |
-05°C÷+55°C |
| Percussion test |
VdÖ |
| Resistenza contro aggrssioni acide o saline |
HB9 |
| Shock test |
din53452 |
| Humidity test |
VdÖ
approved |
| Transient Burst electromagnetick test |
EN50081 / EN50082 |
| |
IEC801-2/ IEC801-3 / IEC801-4 |
| Difesa conseguita con iron box by box |
AISI
Fe426 |
| Combustibilità secondo Norma UL stand 94 |
94HB |
| Contenitore esterno secondo |
Norma UL 94 |
| Classe nel size |
Norma DIN |
| IP
defense |
IP44 |
| Test
Fire Classe "A" TF 2-3-4-5 |
vdÖ
EL14/34/94-30 Prufbericht |
| Housing box color request |
127
colori RAL |
| Altre caratteristiche ai fini CE disponibili a
richiesta |
- Miniboomerang can work beetween 10V dc and 40dc.
- Output
with alarm relay and reversible trouble relay.
|
Absorptions
|
| Electrical worker
|
12V |
24V |
| Posizione jumper 1 -2 |
|
|
| Normal Running |
23mA |
14mA |
| Alarm |
45mA |
24mA |
| Trouble |
50mA |
27mA |
| Posizione jumper 2 -3 |
|
|
| Normal Running |
50mA |
27mA |
| Alarm |
67mA |
37mA |
| Trouble |
32mA |
19mA |
|
Others Features
|
| box
dimensions |
150x80x80 mm. |
| Reflector dim. |
100x100 mm. |
| Swivel lenght |
120
mm. |
| Weight |
500g. |
Setronic
Verona reserves the right to change specification without
notice in order to improve products and manufacturing methods.
Althougt every effort is made to avoid errors we reserve the
right to correct typographical, photographical, clerical or
printing errors.
Certifications
|