ILIA LINE

Highly Sensitive Smoke and Fire detector

The ILIA line is the sum of all the work carried out in line detection and brings truly innovative and unique technology to the market. The basic working principal is that of detection through modulation of the infrared carrier, in addition to this there are a series of technical improvements that make it a high sensitivity Line detector.

The line has two models, a Transmitter/Receiver model and a Reflection system model with the same detection capacity, the same degree of protection IP65 and the same design.

Certifications

The detector was created for market requirements, in particular the industrial market which needs detectors without the need to scale heights on each occasion. With this in mind ILIA can be completely run at ground level by means of a remote control device. The remote control can be used for up to 8 Detectors, even of different types, as well as to carry out adjustments and regulate the outputs of each device from the ground and also check calibration and perform maintenance operations and alarm and fault tests. The connection is a serial RS485 which means installation savings and also subsequent ordinary maintenance savings. ILIA also has accessories such as the internal diaphragm and short circuit insulator for best operation under all conditions.

ILIA can cover distances up to 200 metres in its Transmitter/Receiver version and 150 metres in its Reflection version.

Its “HS” or high sensitivity label confirms how precise and early the detection of these models is with regard both to smoke and to fire. All the models also have double infrared emission to ensure complete signal stability; this feature has solved motorisation difficulties as the angle of alignment for the ILIA is very wide, while detection is precise under all conditions.

The models

ILIA is available in Tx-Rx version (ERHS0712) and in Reflection version (ERRHS0712). The results of planning, technology, design and manufacturing entirely made in Italy.
Can be used in any industrial or civil premise with very easy installation and programming, with very low costs for mounting, cabling and maintenance.
Both models need the Controller CSRLS for programming, calibration and remote test execution. From 2 up to 8 detectors can be connected to the controller by means of expansion boards (SMLS) and also different types (Tx-Rx and Reflection).

ERHS0712 (Tx-Rx) 10 ÷ 200 m
ERRHS0712 (TRx) 10 ÷ 150 m
ERHS0712-1013 (Tx-Rx)
ERRHS0712-1013 (TRx)

The following versions of ilia are available:

ERHS0712-1013 (Tx-Rx)
ERRHS0712-1013 (reflection)
ERHS0712-PRO
White color ERHS0712-1013 (Tx-Rx) – ERRHS0712-1013 (reflection).Equipped with a special SW with possibility of  PRE-ALARM (ERHS0712-PRO).
ERHS0712-PRO-LILIA-OZ
Equipped with a special SW with possibility of PRE ALARM management and provided with a dust proof extension pipe (ERHS0712-PRO-L) to be used only in combination with the Controller PRO version.Now available the new single zone Linear beam detector, ILIA-OZ, consisting of Transmitter-Emitting unit (TRx), the Reflection Unit with swivel and its controller (CSRLS-OZ), included in the package, that allows to manage by the ground all the setting, test and maintenance of the detector, with operative distance from 5 to 80 m with Reflection Unit, from 81 to 100 m with 4 Reflection Units.
ERHS0712-PRO 10 ÷ 200 m
ILIA OZ
ERHS0712-PRO-L 10 ÷ 200 m

Available controller versions (CSRLS)

CSRLS Controller

CSRLS-2
Base version for standard civil and industrial premises, with absence of dust and steam.
CSRLS-2-DUST
Version for installation in critical environments with presence of aerosol, dust, steam.
CSRLS-2-FROST
Special version, ideal for installation in cold storage or environment with presence of water steam or suspended fogs in defrost stages.
CSRLS-2-PRO
To be combined exclusively with the ILIA ERHS0712-PRO model. For installation in VERY critical environment with presence of constant intense steam or dust, where it is necessary to have a double threshold of sensitivity to grant alarm without false signals. To be used only with the insertion of SLMS expansion cards and with the connection of 5 detectors maximum.

CLI Controller

CLI
Base version for standard civil and industrial environments, in the absence of dust, steam or vapors in suspension.
CLI-DUST
Version for installation in environments with intense vapors, dust and suspended aerosols.
CLI FROST
Special version for environments with water vapor or mists in the working phases, open sheds cold storages.
CLI-PRO

For installations in environments where high sensitivity with double alarm thresholds is needed. NOTE version to be combined exclusively with the ERHS0712-PRO or PRO-L models.

Specific Accessories:

SOHI

Protection Case for Detectors of ILIA series ERHS and ERRHS, with pressure cup, to be used in environments where there could be problems given by steam, acid or particular kind of dust or where there is need for cleaning, disinfection, or washing with high pressure jet. Suitable to enforce the protection of the detectors and grant the detectors maintain their continuous high performance in such environments. Use of SOHI does not affect the sensitivity and detection capability of ILIA, protecting and safeguarding from irreparable and permanent damages. 

FAPO

Additional accessory for SOHI overhousing so that it is possible to close it completely in order to avoid accumulations of dust into the front ring.

SACA-G

The adjustable bracket model SACA-G (composed by bracket SAA with PSAG plate) enable to install the beam detector of ILIA or ARGO’s series in the best manner also when the condition of the fixing in the structure to protect are very critics. It is equipped with three knobs to move and settle the plates and fix the extendible part of the bracket. This kind of bracket it’s ideal to have the certainly of stability in every condition , and in particular for fixing on ceilings, concrete beams, side walls or corner.

OVERHOUSING (SOHI)
FAPO
SACA-G BRACKET

ILIA models comparison

This table will be a help in the selection of the correct detector model to be used, depending on the characteristics of the environment that has to be protected. The basic differences between the three main models of this detection systems are highlighted.
For more information please contact our technical department by e-mail laboratorio@setronicverona.com

PERFORMANCE IN LENGTH 10m – 200m

 ILIA + CSRLS-2ILIA + CSRLS-2-DUSTILIA + CSRLS-2-FROSTILIA PRO + CSRLS-PRO
BASIC CONFIGURATION FOR CONNECTING UP TO 2 RECEIVERS 
EXPANSION CARD FOR CONNECTING FROM 3 TO 8 DETECTORS 
EXPANSION CARD FOR THE CONNECTION FROM 1 TO 5 DETECTORS   
PRE-ALARM OUTPUTS   
HIGH SENSITIVITY
REJECTION TO DUST 
MAINTENANCE DISABLED REQUEST OUTPUT    
CONTROLLORECLICLI DUSTCLI FROST
Versione Tx-RxERHS0712 –
ERHS0712-1013
ERHS0712 –
ERHS0712-1013
ERHS0712 –
ERHS0712-1013
Versione TRxERRHS0712 –
ERRHS0712-1013
ERRHS0712 –
ERRHS0712-1013
ERRHS0712 –
ERRHS0712-1013
Dust rejection 
Fog rejection  
Dust proof extension pipe   

Elektronik und Elektrotechnik Made in Italy

Kontakte

SETRONIC Verona S.r.l.

Via Milano,13
37024 Arbizzano di Negrar (VR) - Italia

Tel. +39 045 8347777
Fax +39 045 8347778
E-mail: info@setronicverona.com